Fully IEC-verified and tested low-voltage switchgear assembly

MNS Low-Voltage Withdrawable Switchgear

MNS low-voltage withdrawable switchgear panel for 660 V, 50~60 Hz systems. The main busbar is rated up to 4000 A, and the distribution bus up to 1000 A. Mixed units support power conversion, distribution and control in industrial, transport and utility sites.

660V

Rated Voltage

Max 4000A

Rated Current

Max 50KA

Short-circuit Current

IEC 61439-1/-2

Industrial Standard

Configuration

OEM/ Customizable

FAT Test

Delivery Standard

Technical evaluation

Key Technical Data for Project Configuration

The following table is only a framework for critical performance data for fast project evaluation. The standard configuration range is not a universal promise.

Technical Data Overview

ParameterUnitValue
Rated Working VoltageV380、660
Rated Insulation VoltageV660
Rated Working CurrentA4000
Rated Short-time Withstand CurrentkA50
Rated Withstand CurrentkA105(Peak Value)
Rated Working Current(Vertical Busbar)A1000
Rated Short-time Withstand Current(Vertical Busbar)kA30
Rated Withstand Current(Vertical Busbar)kA63(Peak Value)
Protection (IP)RatingProtection against solidsIP30(>Φ2.5mm)
IP40(>Φ1.0mm)
Protection against dust and splashing water from any directionIP54
Exact evaluation depends on each project’s final electrical rating and protection levels, the model configuration selected in the engineering documents, and the final factory test report; please contact our engineers for project configuration support.

Switchgear Types & Voltage Range

Switchgear Type

Voltage Range

Common Application

Low Voltage (LV)

Up to 1 KV AC

Buildings, factories, data centres

Medium Voltage (MV)

1 kV – 35 kV

Industrial plants, substations, renewable energy plants

High Voltage (HV)

Above 35 kV

Transmission networks, power plants, substations

LV, MV and HV Switchgear Technical Comparison

Parameter

LV Switchgear

MV Switchgear

HV Switchgear

Voltage Range

Up to 1 kV

1 kV – 36 kV

Above 36 kV

Typical Applications

Buildings, Factories

Substations, Industry

Transmission Networks

Interrupting Medium

Air

Vacuum / SF6

SF6 / GIS

Rated Current

Up to 6300 A

Up to 4000 A

Up to 5000 A

Fault Current Rating

Up to 100 kA

Up to 63 kA

Up to 80 kA

Installation Type

Indoor

Indoor / Outdoor

Outdoor / GIS

Protection Complexity

Basic

Medium

Advanced

Maintenance Requirements

Low

Medium

High

Capital Cost

Low

Medium

High

Typical Users

Commercial Facilities

Utilities & Industry

Transmission Operators

Configure Your Switchgear Around Your System

Cabinet Drawing & Outline Dimensions (mm)

Component selection can be adapted to the electrical specification, protection philosophy, installation environment and approved vendor requirements of the project.

Incoming Breaker

Selected according to rated current, fault level and protection requirements.

Copper Busbar

Sized according to current carrying capacity, temperature rise, and short-circuit requirements.

Protection Relay

Protection and monitoring configured according to project requirements.

Metering

Voltage, current, power and energy monitoring options.

Cable Compartment

Cable entry and termination arranged according to site conditions.

MNS Key Applications & Operating Conditions

MNS low-voltage withdrawable switchgear panel for 660 V, 50~60 Hz systems. Used for control of power generation, transmission, distribution, power conversion and power consumption systems.

This product conforms to the standards: GB7251.1“Low-voltage switchgear and controlgear assemblies”, JB/T9661“Low-voltage withdrawable switchgear assemblies”.

Installation & Operating Conditions
Ambient air temperature
  • Less than or equal to 40°C 
  • Less than or equal to 35°C on average over 24 hours 
  • Greater than or equal to -5°C ( -25°C on request)
Altitude
  • Less than or equal to 2000 m
Transportation Temperature
  • Transportation and storage temperatures range from -25°C to +55°C, and can temporarily reach +70°C without causing irreversible damage.
  • If the device is used on marine drilling platforms or in nuclear power facilities, a dedicated technical agreement is required.
Humidity
  • Air should be clean with relative humidity below 50% at +40°C, rising to 90% at +20°C under proper condensation control. 
SSE MNS Features
  • Tested beyond the standards and certified by the most recognized organizations​
  • Segregation up to form 4b type 7​
  • Marine, harsh environment, seismic, vibration, and shock resistance applications​
  • Up to IP54 protection​
  • On-premises condition monitoring and predictive maintenance solution CMES

Switchgear is typically an enclosed system designed to distribute power safely, often connecting to transformers or motor control centres (MCCs), and may include devices such as variable speed drives or power distribution products. Choosing the correct switchgear involves more than matching voltage ratings.

Switchgear Applications Selection Reference

Application

Recommended Switchgear

Commercial Buildings

LV Switchgear

Data Centers

LV Switchgear

Hospitals

LV Switchgear

Manufacturing Plants

LV / MV Switchgear

Mining Operations

MV Switchgear

Renewable Energy Plants

MV Switchgear

Utility Distribution Networks

MV Switchgear

Substations

MV / HV Switchgear

Transmission Networks

HV Switchgear

Power Generation Plants

HV Switchgear

Indoor vs Outdoor Switchgear Selection Reference

Standard

Indoor Switchgear

Outdoor Switchgear

Space Availability

Limited Space

Large Sites

Environmental Protection

Excellent

Moderate

Maintenance Access

Moderate

Excellent

Initial Investment

Higher

Lower

Urban Projects

Recommended

Less Common

Utility Substations

Possible

Common

Environmental Selection Guide

Environment

Recommended Technology

Industrial Plant

Metal-Clad Switchgear

Coastal Area

Corrosion-Resistant Switchgear

Desert Region

Dust-Protected Switchgear

Urban Substation

GIS Switchgear

Renewable Energy Plant

Vacuum Switchgear

High Humidity Area

Sealed GIS Switchgear

Heavy Pollution Zone

GIS / Metal-Enclosed Switchgear

Find Your Path

Customer Role

First Question

What Details Should Care

EPC / System Integrator

Can you meet project drawings, schedule, site standards, and grid-connection requirements?

Project delivery workflow, lead time capability, engineering case studies, scope of delivery, selection parameters, layout drawings, certifications

Distribution Contractor

Is the supplier reliable and quality consistent? Is it easy to procure, install, commission and maintain?

Factory capability, quality control, certifications, brand components, configuration limits, installation dimensions, spare parts, manuals, after-sales terms

Plant Owner / End User

Will it run safely and reduce outage and energy-loss risk? Is it easy to maintain?

Application pain points, reliability data, power quality, maintenance convenience, case studies, warranty, remote monitoring

Distributor / Reseller

Can you support a stable product line and give technical backup? Do you offer supply continuity, customisation, and regional cooperation?

Product line coverage, regional partner policy, MOQ, OEM/ODM options, spare parts support, technical training, catalog downloads, lead time

Technical Engineer

Do rated parameters, protection scheme, and configuration match? Does it meet the local grid code and certification requirements?

Voltage/current/IP/short-circuit ratings, single-line diagrams, cabinet configuration, IEC/UL standards, test reports, downloadable data, FAQ

CUSTOMIZATION

Configured to Your Project Requirements

Align electrical, mechanical, component, and documentation options with your project requirements.
Discuss My Configuration

Electrical

  • Rated Voltage
  • Rated Current
  • Short-Circuit Level
  • Protection Scheme

Mechanical

  • Cabinet Dimensions
  • Cable Entry
  • IP Rating
  • Installation Method

Components

  • Circuit Breaker
  • Protection Relay
  • Metering
  • Communication

Documentation

  • Single-Line Diagram
  • GA Drawing
  • Wiring Diagram
  • Test Report

Tips: Final configuration is confirmed according to approved drawings, project requirements, and destination market needs.

Applications

Switchgear Projects & Applications

Representative project environments and typical configuration needs for low-voltage and medium-voltage distribution systems.

Project Configuration Discussion
Automotive Plant Expansion Project

Automotive Plant Expansion Project

This large-scale vehicle manufacturing plant covers 810,000 m² and features 47 production lines, with an annual capacity of 180,000 vehicles. We supplied MNS-type low-voltage switchgear to provide reliable power distribution for the manufacturing facilities.

380-1000V

Voltage

~4000A

Current

China

Country

Factory

Application

  • Overline
View Details
Multifunctional Sports Hall Project

Multifunctional Sports Hall Project

This multifunctional sports facility has a capacity of 5,000 seats and a gross floor area of approximately 12,000 m². For this project, we supplied MNS-type low-voltage switchgear to provide a reliable low-voltage power distribution solution.

380-1000V

Voltage

~4000A

Current

Cameroon

Country

Sports Hall

Application

  • Overline
View Details
Airport Runway and Supporting Facilities Expansion Project

Airport Runway and Supporting Facilities Expansion Project

Airport Phase III Expansion Project. We supplied MNS-type low-voltage switchgear to provide reliable power distribution for the airport’s expansion and supporting facilities.

380-1000V

Voltage

~4000A

Current

China

Country

Airport

Application

  • Overline
View Details
Why Choose SSE Electric

Quality Control You Can See Before Shipment

Every switchgear cabinet leaving our facility must pass a five-stage quality assurance process, from raw materials to final shipment release. 

Verified Components Before They Enter Your Switchgear

We verify all purchased components, such as circuit breakers, transformers, insulators, busbar material, and auxiliary devices, against approved vendor lists and inspect them upon receipt.
01

Certificates & Test Data

Verify the certificates of conformity, type test reports, and factory test data.

02

Inspecting Structural Parts

Conduct dimensional and visual inspection of busbars, enclosures, and structural parts.

03

Testing Insulating Materials

Run sampling tests on insulating materials and other components.

04

Reject Defective Parts

Prevent defective components from entering the production line to safeguard the original reliability.

Precision Assembly That Meets the Drawing

Component assembly must strictly follow standard operating procedures to ensure worker safety while maintaining a clean, dust-free workshop environment.
01

Torquing Every Bolted Connection

Tighten all bolted joints to the specified torque values and record each connection point for traceability.

02

Verifying Clearances & Phase Sequence

Check conductor clearances, creepage distances, and phase sequence against design drawings.

03

Testing Shutters, Interlocks & Truck Mechanisms

Verify shutters, interlocks, and the truck’s mechanical performance in different positions: service, test, and withdrawn.

04

Checking Wiring Against Schematics

Check all internal wiring against schematics, including ferrule identification, terminal tightening, and earthing continuity.

Every Panel Proves Safe in Electrical Verification

Before any energization, each panel undergoes a comprehensive program of routine tests in accordance with IEC 60298 and GB 3906.
01

Measuring Main Circuit Resistance

Measure the main circuit resistance.

02

Applying Withstand Voltage Tests

Run a power-frequency withstand voltage test on the main circuit and auxiliary circuits.

03

Measuring Partial Discharge

Verify misoperation-prevention functions; detect partial discharge where specified.

04

Relays & Metering Testing

Test protection relays by secondary injection and verify metering accuracy.

Nothing Ships Only With Approval

The FAT confirms that the switchgear is built in conformity with the approved drawings, the technical specification, and all applicable standards.
01

Repeating Comprehensive Checks

Perform visual and mechanical checks; verify design drawings, test procedures, and technical documents.

02

Running Key Tests Per Standards

Conduct tests per IEC standards and project specs, including 1st/2nd injection tests and corrosion-resistance tests, etc.

03

Re-Testing Before Release

Record deviations or non-conformities during FAT, take corrective measures, and re-test until all units pass before release.

04

Preparing Before Shipping

Issue the FAT report and release certificate; clean the cabinet surface.

From Our Factory Floor to Your Site, Intact and On Time

Shipment isn’t simply switchgear dispatched. Every step follows a controlled process covering final verification, export-grade protection, document preparation, and coordinated logistics.
01

Packing for Export

Pack each cabinet in export-grade packaging with moisture proofing and shock absorbers.

02

Coordinating the Logistics

Manage the entire transport chain —booking, routing, and customs coordination—to ensure on-time delivery to the site.

03

Documentation Preparing

Photograph and record packaging, loading, and container sealing.

04

Delivering the Full Dossier

Complete the documentation package for every shipment, including the spare parts list.

Specific Visual Evidence

Global Electrical Industry Partners & Customers

Provide customers with production line technical consultation, engineering design, design selection, engineering budgeting, factory automation, full-process training, installation, commissioning, and turnkey solutions for the entire factory.

Engineer Online

+86 123 456 7890

Quality & Compliance

Standards & Certifications

Use this space to add a medium-length description. Be brief and give enough information to earn their attention.

  • IEC 62271-200
  • IS09001
  • CE Certificate
  • FAT Report
  • CE Certificate
  • FAT Report

Sample documents available upon request.

View Full Certificates
OEM & ODM WORKFLOW

From Project Requirements to Delivered Electrical Equipment

Confirm final electrical ratings and configurations against the project specification and approved engineering documents.

Built for Fast, Safe Grid & Plant Integration

Here are common questions about MNS low-voltage withdrawable switchgear. Our engineering team is also available to discuss technical requirements specific to your project.

Talk to Our Technical Butler Team

Send the information you already have. We will help organise the rest.

* fields help us return a quick response to you as soon as possible.

MNS switchgear features a modular withdrawable design that allows individual functional units to be moved between service, test, and withdrawn positions. This makes inspection, maintenance, and unit replacement more convenient, while helping reduce disruption to other sections of the switchboard. Its flexible compartment arrangement also supports different power distribution and control requirements within the same assembly.

MNS low-voltage withdrawable switchgear is suitable for power distribution, conversion, and control systems in manufacturing plants, transportation facilities, and utility installations. Typical applications include industrial production lines, airport facilities, and large public buildings where flexible circuit arrangements and convenient maintenance are important.

The withdrawable design allows individual functional units to be isolated and accessed without necessarily dismantling the entire switchboard. Whether other sections can remain energized during maintenance depends on the busbar arrangement, compartment segregation, protection scheme, and site operating procedures. All work must follow the manufacturer’s isolation instructions and applicable electrical safety requirements.